Specifications (200-230V class)
Model :SV004iC5-1 SV008iC5-1 SV015iC5-1 SV022iC5-1
Motor rating [HP] : 0.5 ; 1 ; 2 ; 3
[kW] : 0.4 0.75 1.5 2.2
Output ratings Capacity[kVA] : 0.95 1.9 3 4.5
FLA[A] : 2.5 5 8 12
Voltage : Three phase, 200 to 230V
Frequency : 0 to 400Hz
Input ratings Voltage : Single phase, 200 to 230V ( ±10% )
Frequency : 50 to 60Hz ( ±5% )
Control
Control method : V/F control, Sensorless vector control
Frequency setting resolution : ∙Digital reference : 0.01Hz ∙Analog reference : 0.06Hz/60Hz
Frequency setting accuracy : ∙Digital : 0.01% of Maximum output frequency ∙Analog : 0.1% of Maximum output frequency
V/F ratio : Linear, Squar pattern, User V/F
Overload capacity : 1min. at 150%, 30sec. at 200% ( with inverse characteristic )
Torque boost : Manual( 0 to 15% adjustable ), Auto
Operation
Input signal Operator control : Keypad / Terminal / Communications
Frequency setting : ∙Analog : 0~10V/4~20mA ∙Digital : Keypad ∙Communication : RS485
Start signal : Forward / Reverse
Multi-step : Setting up to 8 speeds ( use multi-function terminal )
Multi-step accel : 0.1~6000 sec. Max. 8 types available by multi-function terminal
/decel time : Selectable accel/decel patterns : Linear, U and S
Emergency stop : Interrupting the output of the drive
Jog : Jog operation
Fault reset : Reset the fault when protective function is active
Output signal Operation status & : Frequency detection, Overload alarm, Stalling, Overvoltage, Undervoltage,
Fault output : Drive overheating, Run, Stop, Constant speed, Speed searching,
Fault output ( Relay and Open collector output )
Indicator : Choose one from output frequency, current, voltage and DC voltage.(Output voltage : 0~10V )
Operation : DC braking, Frequency limit, Frequency jump, Second function,
function : Slip compensation, Reversing prevention, Auto restart, PID control
Protection functions
Drive trip : Overvoltage, Undervoltage, Overcurrent, Drive overtemperature, Motor overtemperature, I/O phase loss, I/O mis-wiring, Overload , External device fault 1.2, Loss of speed command, Hardware fault, Communication error, CPU error
Drive alarm : Stall prevention, Overload alarm
Momentary : ∙Less than 15 msec : keeping operation
power less : ∙More than 15 msec : auto restart available
Display keypad
Operation information : Output frequency, current and voltage, Set frequency value, Operation speed, DC voltage
Trip information : Display the trip cause when the protection function activates. Recent 5 faults records stored
Environment
Operating ambient temp : -10℃ ~ 50℃
Storage temperature : -20℃ ~ 65℃
Humidity : 90%Rh max.(non condensing)
Altitude & Vibration : 1000m max, 5.9m/sec2(0.6g) max.
Atmosphere : No corrosive gas, flammable gas, oil mist or dust
Pressure : 70~106k Pa
Silahkan hubungi kami:
B&C Multi Solusi
*Note: Harga Aktual via telepon